Power outages and backup power
What Size Generator Do I Need - Running and Starting Watts, With the Math
Updated October 12, 2026 - 9 min read - Rainy Day Plan
The short answer
Add the running watts of everything that must run at the same time, plus a margin - that's the running size. Then add the extra starting watts of the one motor that needs the most to start - that's the starting size. A home with a well pump, fridge, freezer, gas furnace fan and a few lights needs about 2,000 running and 5,000 starting watts.
Every generator has two ratings, and you need both
Running watts, also called rated or continuous watts, is what the generator can deliver hour after hour. Your whole running load has to fit under that number. Never run it past the maker's rating.
Starting watts, also called surge or peak watts, is a short burst. Motors need it. A fridge, freezer or air conditioner can pull two to three times its normal watts while the motor starts. When you don't have the real figure for a motor, plan on four times. That's why a generator that looks big enough on paper can stall the moment the well pump kicks in.
Bigger units are rated in kilowatts. One kilowatt (kW) is 1,000 watts.
Your own labels beat any chart
You don't need a meter.
- Read the label. The watts are on the appliance's serial plate or in its manual.
- No watts listed? Multiply the amps by the volts on the same plate. A label that says 6 amps at 120 volts means 6 x 120 = 720 watts.
- For starting watts, look in the manual or ask the maker. For a well pump, ask the company that installed it. Many labels leave this number out.
Charts and rules of thumb are for when you have nothing else, and they don't agree with each other. Take a 1/3 horsepower well pump. A rule of thumb of about 1,000 watts to run for every horsepower puts it at roughly 330 watts running. A utility's chart lists the same pump at 1,000. That's three times apart, and only the label on your own pump can settle it.
The sum, in five lines
- List what must run at the same time during an outage. Not everything you own.
- Add up the running watts. That's your running total.
- Multiply the running total by 1.25. The result is the smallest running rating to shop for. The 1.25 is our own planning margin, the same one our outage guide and calculator use, and it leaves room for a load you forgot to list.
- Find the one item with the highest additional starting watts and add that to the running total. The result is the starting rating to shop for.
- Check the volts. More on that below.
There's a trap in line 4. Some charts and manuals give additional starting watts - the extra on top of running. Others give the total at start-up. The tables on this page give additional. If your number is a total, subtract that item's running watts before you add it, or you'll count your biggest motor twice.
Line 4 is only as good as the starting number you feed it. If it came from the manual, the maker or the installer, you're done. If it came from a chart of typical values, or you have no number at all, run one check. Take the motor with the most running watts, count it at four times those watts, and add the running watts of everything else. Then shop for whichever starting figure is higher, the chart's or the check's. A chart can't know your pump, and too little starting power is what stalls a generator.
A worked example: a house on a well in a winter outage
This is an example, not your house. The watts are typical values from a public utility worksheet, so you can check each one. Swap in your own labels.
| What must run | Running watts | Additional starting watts |
|---|---|---|
| Refrigerator/freezer | 700 | 2,200 |
| Well pump, 1/3 hp | 1,000 | 2,000 |
| Furnace fan, 1/3 hp | 700 | 1,400 |
| Four LED bulbs, 15 W each | 60 | - |
| Two phone chargers, 20 W each | 40 | - |
| Laptop | 60 | - |
| Total | 2,560 | highest: 2,200 |
Running size: 2,560 x 1.25 = 3,200 watts.
Starting size, by the chart: 2,560 + 2,200 = 4,760 watts.
One surprise on this sheet: the fridge, not the pump, has the biggest starting jump. But these are typical values, not this house's labels, so the check applies. The pump has the most running watts. Count it at four times: 1,000 x 4 = 4,000, plus 1,560 for everything else.
Starting size, by the check: 5,560 watts.
The check is higher, so it wins. For this list, shop for about 3,200 running watts and about 5,600 starting watts. In kilowatts that's 3.2 and 5.6. That lands close to the round numbers at the top of this page: about 5,000 watts at the peak, with about 2,000 for continuous running.
On a generator's spec sheet you'll meet those same two numbers. Match its running (rated) watts to your running size and its starting (surge or peak) watts to your starting size, and see that each is at least as big as yours.
Now take the pump off the list, as in a house on city water. The running total drops to 1,560 watts. Running size: 1,560 x 1.25 = 1,950. Starting size: 1,560 + 2,200 = 3,760. This time the check comes out lower - the fridge at 700 x 4 = 2,800, plus 860 for the rest, is 3,660 - so the chart's figure stands. That's a much smaller machine. And if your list is only a fridge and a few small things, a battery may do the job with no engine at all.
Typical watts for the other things on your list
Here are more lines from the same worksheet. They're typical values too, and the label on your own machine beats any of them.
| Appliance | Running watts | Additional starting watts |
|---|---|---|
| Sump pump, 1/3 hp | 800 | 1,300 |
| Sump pump, 1/2 hp | 1,050 | 2,200 |
| Window air conditioner, 12,000 BTU | 3,250 | 3,950 |
| Space heater | 1,500 | - |
| Electric water heater | 4,500 | - |
| Microwave oven, 1,000 watts | 1,000 | - |
| Coffee maker | 1,000 | - |
| Toaster oven | 1,200 | - |
| Computer with monitor | 800 | - |
A dash means the worksheet gives no starting number for that line.
The sum counts one motor starting at a time, so start them that way
The sum adds a single starting surge. That holds only if your motors don't all start in the same second.
Start the largest motor first and add other loads once each motor is up to speed. You can't schedule a well pump or a furnace fan, though. They start when they want to, so they're the ones your starting rating has to cover. If both could start in the same moment, add both of their extra starting watts to the starting size.
A 240-volt pump won't run from a 120-volt generator
Most appliances run on 120 volts. Some large ones, such as ovens, clothes dryers and well pumps, are rated at 240 volts, and a portable generator may put out 120 volts only or both. Read the pump's label before you shop.
A pump or furnace fan is wired into the house, so no extension cord reaches it. It can take generator power only through a transfer switch or interlock that a licensed electrician installs under a permit. The switch cuts the house off from the utility lines. That protects the line workers repairing them, and without it the generator can be ruined by overloading. Never plug a generator into a wall outlet or the panel. Where the machine sits on outage day is in what to do when the power goes out, and the carbon monoxide alarms that go with it are on the power outage emergency kit list.
A whole-house standby unit is sized by the electrician's load calculation
For a standby generator with an automatic switch, the size doesn't come from a rule of thumb. It comes from a load calculation that goes in with the permit. In one Florida city, for example, the permit needs an itemized list of the loads the generator will serve, with motor start-up current counted. And the load, calculated under Article 220 of the National Electrical Code, can't go over the generator's rating.
Your own list from the five lines above is still worth making first. It tells you whether you want the whole house or only the essentials.
Why our outage guide lists a fridge at about 60 watts
Our printable outage guide plans a fridge at 60 watts over 24 hours, which is 1,440 watt-hours a day. That's an average around the clock, because the compressor cycles on and off. It's our planning number for battery math, not a label reading.
A generator has a different job. It must carry the fridge while the compressor runs and get through the jolt when it starts. So for a generator, use label watts and starting watts. For a battery, use the daily average to see how many watt-hours it has to hold, then check that its running and surge watts can still start the fridge. Neither number is wrong.
In an RV, the plug sets the ceiling and the air conditioner sets the size
The five lines work the same in an RV, a camper or a travel trailer. What changes is the plug, and which motor needs the most to start.
Start with the RV's own plug. It tells you the most the RV can ever draw, and the math is amps times volts again, like any label. A 30 amp RV plug has three prongs and one 120-volt line: 30 x 120 = 3,600 watts. A 50 amp plug has four prongs and two 120-volt lines of 50 amps each: 2 x 50 x 120 = 12,000 watts. Don't shop for that number. It's a ceiling, and your list of what must run together still sets the size.
The motor with the biggest start is nearly always the roof air conditioner. A generator can carry the fridge, the lights and the water pump with room to spare and still stall when the air conditioner starts. If neither its label nor its manual gives a starting figure, ask its maker for one first. Only then fall back on the line 4 check: four times its running watts, plus the running watts of everything else. That check runs high for many roof units, so a figure from the maker can save you buying a bigger, heavier and louder generator than you need. When you switch things on, start the air conditioner first, with the rest off, and add loads once it's running. Some loads switch on by themselves the moment the RV is plugged in: the battery charger, and a fridge or water heater left set to electric. Put them on the list, or switch them to off or to gas before you start the air conditioner. Two air conditioners mean two big motors. If you need both running, both go on the list. If you don't, run one at a time.
The plug also has to fit the generator. A 30 amp RV plugs into a generator's 30 amp RV outlet. A 50 amp RV needs a 50 amp outlet that gives both lines, or an adapter down to 30 amps. Even with both lines, each gets about half of what the generator makes, so split the big loads between them. With the adapter, the whole RV shares 3,600 watts at most, less if the generator makes less, and you're back to the 30 amp math. Up in the mountains or on a hot day, a generator puts out less than its label says. Its manual tells you how much less, so take that off before you compare. If you camp with no hookups at all, so the generator and the batteries carry everything, the day-to-day sums are on our boondocking page.
Any size makes carbon monoxide: 20 feet from the house
Size doesn't change this part. A portable runs outdoors only, at least 20 feet from the house, with its exhaust aimed away from windows, doors and vents. It never runs in a garage, basement, crawlspace or shed, and not on a porch or in a carport. Put battery-powered carbon monoxide alarms on every level of the home.
At a campsite, keep the generator as far from the RV's door, windows and roof vents as you would from a house, and point the exhaust away from the campers next to you too. Keep a working carbon monoxide alarm inside the RV, test it, and change its batteries on schedule.
Sources
Every number in this article comes from these public sources, and we checked each one before it went up.
- NDSU Extension - Standby electric generators
- Eugene Water & Electric Board (EWEB) - Generator sizing considerations, worksheet
- San Diego Gas & Electric (SDG&E), hosted by the City of San Diego - Facts you should know about portable electric generators, 2004
- Utah Be Ready - Generator
- City of North Port, Florida, Building Division - Generator permit guidelines
- CDC - Carbon monoxide poisoning basics
- CPSC - Caution when using portable generators, Tropical Storm Ian, 2022
- Ready.gov - Power outages
- Tennessee State Fire Marshal's Office - State Fire Marshal warns campers about carbon monoxide dangers, July 17, 2015